User Manual of A90 Series Inverter 258 communication cable is disconnected. E17 Abnormality of inverter temperature sensor The inverter temperature sensor is disconnected or short-circuited. 1. Check whether the inverter temperature sensor is connected properly. 2. Seek technical support. E18 The soft start relay is not engaged. 1. The power supply fails during operation. 2. The input power supply is subject to phase loss. 3. The terminals of the input power supply are loose. 4. The voltage of the input power supply drops too much. 5. The switch contacts of the input power supply are aging. 1. Stop the inverter before power-off, or directly reset the fault. 2.
Check the input power supply and wiring. 3. Tighten the screws of input terminals. 4. Check the air circuit breaker and contactor. E19 Error of current detection circuit The detection circuit of the drive board or control board is damaged. 1. Seek technical support. E20 Stall fault 1. The deceleration time is too short. 2. Error of dynamic brake for deceleration. 3. The load is too heavy. 1. Increase the deceleration time. 2. Check the dynamic brake. 3. Check whether the motor cannot be stopped as it is driven by another load. E21 PID feedback disconnection 1.
The PID feedback is greater than the upper limit (F09.24) or less than the lower limit (F09.25), depending on the type of the feedback sensor. 1. Check whether the feedback line falls off. 2. Check whether the sensor is working abnormally. 3. Adjust the detection value of feedback disconnection to a reasonable level. E24 Self-identification error 1. Press the STOP/RESET key during parameter identification. 2. The external terminal stops working (FRS = ON) 1. Press the STOP/RESET key to reset. 2. The external terminal should not be operated during parameter identification.