User Manual of A90 Series Inverter 257 deceleration time is too short. 2. In the V/F drive mode, the V/F curve setting is unreasonable. 3. The load is too heavy. 4. The braking time is too long, the braking intensity is too high, or DC braking is enabled repeatedly. deceleration time. 2. Reasonably set the V/F curve. 3. Use the inverter that matches the load. 4. Reduce the braking time and braking intensity. Do not enable DC braking repeatedly. E10 Inverter overheat 1. The ambient temperature is too high. 2. The inverter is subject to poor ventilation. 3. The cooling fan fails. 1. The operating environment of the inverter should meet the specifications. 2.
Improve the ventilation environment and check whether the air duct is blocked. 3. Replace the cooling fan. E11 Parameter setting conflict 1. There is a logic conflict in parameter settings. 1. Check whether parameters set are illogical before the occurrence of fault. E13 Motor overload 1. The acceleration and deceleration time is too short. 2. In the V/F drive mode, the V/F curve setting is unreasonable. 3. The load is too heavy. 1. Increase the acceleration and deceleration time. 2. Reasonably set the V/F curve. 3. Use a motor matching the load. E14 External fault 1. The external device fails, resulting in the terminal action. 1. Check the external device. E15 Inverter memory failure 1.
Interference results in memory reading and writing errors. 2. The internal memory of the controller is read and written repeatedly, causing damage to the memory. 1. Press the STOP/RESET key to reset the controller and try again. 2. For the parameters (e.g. frequency setting) to be modified frequently, set F10.56 to 11 after debugging. E16 Communication error 1. Communication timeout is enabled in the discontinuous communication system. 2. Communication is disconnected. 1. F10.03 is set to 0.0 in the discontinuous communication system. 2. Adjust the F10.03 communication timeout. 3. Check whether the