User Manual of A90 Series Inverter ★ When BR100-160 works with the minimum resistance, the braking unit can work continuously at the braking frequency D=33%. In the case of D>33%, the braking unit will work intermittently. Otherwise, an over-temperature protection fault will occur. 11.3 Selection of Connecting Wires Since all braking units and braking resistors work at high voltage (>400VDC) and in the discontinuous status, please select appropriate wires. See Table 0-1 for the wiring specifications of the main circuit. Use the cables with the conforming insulation levels and cross-sections.

Table 0-1 Wire Specifications of Braking Units and Braking Resistors Flexible cables have higher flexibility. Because cables may be in contact with high-temperature devices, it is recommended to use copper-core and heat-resistant flexible cables or flame-retardant cables. The braking unit should be close to the inverter as much as possible and no more than 2m far away from the inverter. Otherwise, the DC-side cables should be twisted and used with magnetic rings to reduce radiation and inductance. The lengths of connecting wires of the braking unit, braking resistor and inverter are shown in Fig. 0-1.

269 Minimum Peak Applicable Model and specification Average Braking Current I (A) av Application Resistance Current Inverter Power (Ω) I (A) max (kW) BR100-045 Energy consumption braking 10 45 75 18.5 - 45 BR100-160 Energy consumption braking 6 75 150 55 - 160 Specification Average Braking Current I (A) av Peak Braking Current Cross-section (mm2) of and model I (A) max Copper-core Cable BR100-045 45 75 10 BR100-160 75 150 16 BR100-315 120 300 25