User Manual of A90 Series Inverter Chapter 12 MODBUS Communication Protocol 12.1 Applicable Scope 1. Applicable series: A90 series 2. Applicable network: Support the “single-master multi-slave” communication network with MODBUS-RTU protocol and RS-485 bus. A+ A- Host A- A+ A+ A- A+ A- A+ A- Inverter 1# Inverter 2# Inverter n# 12.2 Interface Mode RS-485 asynchronous half-duplex communication mode, with the least significant bit sent first; RS-485 network address: 1-247; 0 is the broadcast address; 1-8-N-2, 1-8-E-2 and 1-8-O-2); Default data format of RS-485 terminal: 1-8-N-1 [ 2 ] (options: 1-8-E-1, 1-8-O-1, Default baud rate of RS-485 terminal: 9600bps (options:
4,800bps, 19,200bps, 38,400bps, 57,600bps and 115,200bps) It is recommended to use twisted-pair shielded cable as the communication cable to reduce the impact of external interference on communication. [2] : 1-8-N-1, meaning 1 start bit - 8 characters per byte of data - no parity - 1 stop bit. E: even parity. O: odd parity. 12.3 Protocol Format 12.3.1 Message format As shown in Fig. 0-1, a standard MODBUS message includes a start tag, RTU 271