User Manual of A90 Series Inverter 12.3.3.5 0x06: function code used to write a single register or command In the remote terminal unit, this function code is used to write a single holding register. The request PDU describes the address to be written to the register. The normal response is the response made to the request, which is returned after the register content is written.  Request PDU  Response PDU  Error PDU Below is an example of a request to change the drive control mode of the motor 1 (F00.01) to “1: SVC”. ★ The function code 0x06 cannot be used if modified frequently, in order to avoid damage to the inverter.

280 code Lo Data Hi A5 Data Hi A5 Data Lo 37 Data Lo 37 Function code 1 byte 0x06 Address of register 2 bytes 0x0000 - 0xFFFF Register value 2 bytes 0x0000 - 0xFFFF Function code 1 byte 0x06 Address of 2 bytes 0x0000 - 0xFFFF register Register value 2 bytes 0x0000 - 0xFFFF Error code 1 byte 0x86 Exception code 1 byte See Table 0-4 Request Respond Domain name (0x) Domain name (0x) Domain name (0x) (normal) (abnormal) Function 06 Function 06 Function 86 Register address Hi 00 Register address 00 03 Hi Exception Register address Lo 01 Register address 01 code Lo Register value Hi 00 Register value Hi 00 Register value Lo 01 Register value Lo 01