User Manual of A90 Series Inverter 12.3.4 Register address distribution Table 0-2 Detailed Definition of Register Address of MODBUS Protocol 283 Address Space Note For the function code FXX.YY, the high order is hexadecimal of XX and the low order is hexadecimal of YY. For example, the address of F00.14 is 000EH (00D=00H, 14D=0EH). Function code 0000H - 6F63H When the parameters are set with the function code 0x06 or 0x10, the function that “the settings are valid immediately and not saved after power-down” can be realized in the form of “original address +8000H”. For example, the corresponding address of F00.14 is 800EH (=000EH+8000H).
Function code (not saved after power-down) 8000H-EF63H 7000H control word 0000H Invalid command 0001H Forward running 0002H Reverse running 0003H JOG forward 0004H JOG reverse 0005H Deceleration to stop 0006H Stop the controller quickly 0007H Free stop 0008H Fault resetting 0009H +/- input switching 000BH JOG stop Others to 00FFH Reserved Control 7001H Communication percentage setting of main channel frequency A -100.00% to 100.00% (100% = maximum frequency) comman d (write only) 7000H 7002H Communication percentage setting of auxiliary channel frequency B -100.00% to 100.00% (100% = maximum frequency) ~ 71FFH 7003H Torque communication setting -200.00% to 200.00% (100% = digital torque setting) 7004H Communication setting of process PID setting -100.00% - 100.00% 7005H Communication setting of process PID feedback -100.00% - 100.00% 7006H Voltage setting of 0.00% to 100.00% (digital setting reference)