User Manual of A90 Series Inverter N* = number of registers Response PDU Error PDU from F03.00 (i.e. setting the Y1 output terminal function): Below is an example of a request to write 00 01 and 00 03 into two registers starting ★ The function code 0x10 cannot be used if modified frequently, in order to avoid damage to the inverter, as detailed in 0.
282 Function code 1 byte 0x10 Starting Address 2 bytes 0x0000 - 0xFFFF Number of 2 bytes 1 - 16 registers Error code 1 byte 0x90 Exception code 1 byte See Table 0-4 Request Respond Domain name (0x) Domain name (0x) Domain name (0x) (normal) (abnormal) Function 10 Function 10 Function 90 Starting address Hi 03 Starting address 03 03 Hi Exception Starting address Lo 00 Starting address 00 code Lo Number (Hi) of registers 00 Number (Hi) of 00 registers Number (Lo) of registers 02 Number (Lo) of 02 registers Number of bytes 04 Register value Hi 00 (F03.00) Register value Lo 01 (F03.00) Register value Hi 00 (F03.01) Register value Lo 03 (F03.01)