User Manual of A90 Series Inverter address, frame error, etc.), no response will be returned. This will be regarded as a timeout by the slave station. If the slave station receives a request without communication error but cannot process the request (e.g. a request to read the non-existent register), the slave station will return an exception response and the master station will be informed of the actual error. The exception response message has two fields different from those of the normal response: Function code field: In the normal response, the slave station copies the function code of the original request in the corresponding function code field.
The MSB values of all function codes are 0. In the exception response, the MSB of the function code is set to 1 by the slave station. That is, the exception response function code = normal response function code + 0x80 . Data field: The slave station can return the data from the data field in the normal response and exception code in the exception response. For the defined exception codes, see Table 0-4 Definitions of Exception CodesTable 0-4. Table 0-4 Definitions of Exception Codes 293 Exception Item Meaning code 01H Illegal function The function code received by the slave station (inverter) is beyond the configured range (see 12.3.3 Function code).
02H Illegal data address The data address received by the slave station (inverter) is not allowed. In particular, the combination of the start address of the register and the transmission length is invalid (see 12.3.4 Register address distribution). 03H Illegal data frame The slave station (inverter) has detected the incorrect query data frame length or CRC check. 04H Slave failure When the slave station (inverter) tries to execute a requested operation, an unrecoverable error occurs. This may be caused by the logic error, failure to write to the EEPROM, etc.
05H Data over-range The data received by the slave station (inverter) is not between the minimum and maximum values of the corresponding register. 06H Parameter read-only The current register is read-only and cannot be written. 07H Unchangeable When the inverter is in the running status, the current register