User Manual of A90 Series Inverter 12.4 Protocol Description 12.4.1 Definition of inter-frame and intra-frame time interval A complete MODBUS message contains not only the necessary data units, but also the starting and ending tags. Thus, as shown in Fig. 0-1 or Fig. 0-3, the idle level with a transmission time of 3.5 characters or more is defined as the starting and ending tag. If there is an idle level with a transmission time of more than 1.5 characters during message transmission, the transmission will be deemed exceptional. Specific starting/ending and exception intervals are related to the baud rate, as detailed in Table 0-5.

If the baud rate is 9,600bps and the sampling period is 1ms, the starting and ending time interval is the idle level of 4ms or more (3.5Ч10/9600=3.64≈4), and the exceptional data interval is the idle level in which the interval of data bits of one frame is greater than or equal to 2ms (1.5Ч10/9600=1.56≈2) and less than 4m (the idle level of normal data bits is less than or equal to 1ms). Table 0-5 Correspondence between Time Interval and Baud Rate (t adjust =1ms) 294 parameter in running cannot be written. If necessary, please shut down the inverter. 08H Parameter protection by password The current register is protected by a password.

Starting and Exception Baud Rate ending time interval Remarks (bps) interval T exception T (t ) interval adjust (t ) adjust 4800 8 4 The idle level of 3ms or less is allowed for a normal frame. When the idle level is 8ms or greater, it indicates the end of a frame of data. 9600 4 2 The idle level of 1ms or less is allowed for a normal frame. When the idle level is 4ms or greater, it indicates the end of a frame of data. 19200 2 1 The idle level of less than 1ms is allowed for a normal frame. When the idle level is 2ms or greater, it indicates the end of a frame of data. Higher 1 1 When an idle level of 1ms appears, it indicates the end of a frame.