Delta Electronics AH — MC_VelocityControl

AH Motion Controller – Motion Control Instructions Manual Motion diagram: MC_VelocityControl M2 ( Execute M20 ( InVelocity M21 ( Busy M22 ( Active M23 ( CommandAborted M24 ( Error M25 ( ErrorID MC_Stop _3 M3 ( Execute - When M2( Execute ) changes to True, MC_VelocityControl drives the axis to the target velocity. When the axis reaches the specified target velocity, M20( InVelocity ) changes to True. - When M3( Execute ) changes to True, MC_Stop aborts MC_MoveVelocity and the axis decelerates according to the deceleration rate specified by MC_VelocityControl. - If the MC_VelocityControl is not aborted, it will stay at the specified target velocity, and M20( InVelocity) remains True.

 BufferMode BufferMode determines the behavior to combine the axis motions for this instruction and the previous instruction. When the instruction is executed; - The selected buffer mode is valid if the previous instruction is executing. - The selected buffer mode is invalid if the axis is in “Standstill” state. The following table lists the available buffer mode settings of MC_VelocityControl. 3-92 ) ity) y) ) ed) ) p ) ity et city Time Deceleration is performed by the deceleration rate of MC VelocityControl. _ Deceleration is performed by the deceleration rate of MC VelocityControl. _ Buffer Mode Function 0: mcAborting Aborts the ongoing motion.

The next instruction takes effect immediately 1: mcBuffered Automatically executes the next instruction after the ongoing motion is completed.