Chapter 3 Motion Control Instructions Outputs 3_ Outputs Update Timing 3-97 Name Function Data type Output range (Default value) InTorque True when the specified torque or force is reached. BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Active True when the axis is being controlled. BOOL True/False (False) CommandAborted True when the instruction is aborted. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code when the error occurs. Refer to Appendices for error code descriptions.
DWORD 16#0~16#FFFFFFFF (0) Name Timing for shifting to True Timing for shifting to False InTorque When the specified target torque is reached. When Error shifts to True. When CommandAborted shifts to True. When the instruction is re-executed and the target torque is changed. Busy When Execute shifts to True. When Execute changes to False. When Error shifts to True. When CommandAborted shifts to True. Active When the motion on the axis is started. When Execute changes to False. When Error shifts to True. When CommandAborted shifts to True. CommandAborted When this instruction is aborted by another instruction with the Buffer Mode set to mcAborting.
When this instruction is aborted because of the execution of MC Stop _ instruction. When Execute changes to False. If Execute is False and CommandAborted shifts to True, it will be True for only one period and immediately shift to False. Error/ErrorID When an error occurs in the execution conditions or input values for the instruction.(Error code is recorded) When Execute shifts from True to False. (Error code is cleared)