Delta Electronics AH — MC_SetOverride

AH Motion Controller – Motion Control Instructions Manual MC_SetOverride  Inputs _3  Outputs 3-116 FB/FC Description FB MC SeOverride changes the velocity override factors so as to change the target velocity of a motion axis. _ Name Function Data type Setting value (Default value) Timing for updating Enable The axis is ready to be operated when Enable is True. When Enable is True, override factor will be continuously updated. BOOL True/False (False) - VelFactor Defines the velocity override factor. (Unit: %) LREAL 0 to 500 (100) Continuously updates value during busy state.

AccFactor (Reserved) Reserved - - - JerkFactor (Reserved) Reserved - - - Name Function Data type O utput range (Default value) Enabled True when the axis is ready to be operated. BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to Appendices for error code descriptions DWORD 16#0~16#FFFFFFFF (0)