Delta Electronics AH — MC_Reset

Chapter 3 Motion Control Instructions MC_Reset MC_Reset is used to make the state transition from “ErrorStop” to “Standstill” or “Disabled” by clearing all axis-related errors while keeping the output of the function block instruction.  Inputs 3_  Outputs  Outputs Update Timing 3-141 FB/FC Description FB MC Reset clears axis-related errors _ Name Function Data type Setting value (Default value) Timing for updating Execute Executes the instruction when BOOL True/False - Execute changes to True. (False) Name Function Data type Output range (Default value) Done Indicates the completion of the axis error reset process, i.e. entering “Standstill” or “Disabled” state.

BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Error True if an error occurs BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to t Appendices for error code descriptions DWORD 16#0~16#FFFFFFFF (0) Name Timing for shiftng to True Timing for shifting to False Done  When axis error reset process is completed.  When Execute shifts from True to False.  If Execute is False and Done shifts to True, it will be True for only one period and immediately shift to False. Busy  When Execute shifts to True  When Done shifts to True.  When Error shifts to True.

Error/ErrorID  When an error occurs in the execution conditions or input values for the instruction.(Error code is recorded)  When Execute shifts from True to False. (Error code is cleared)