Chapter 3 Motion Control Instructions Outputs Outputs Update Timing 3_ Timing Diagram Execute Done Busy Error Error ID Troubleshooting - If an error occurs during the execution of the instruction or when the axis is in the state of “Errorstop”, Error will change to True and the axis will stop moving. You can refer to ErrorID (Error Code) to address the problem. - Information regarding error codes and indicators are attached as Appendices for a quick reference. The detailed troubleshooting procedures are explained in AH Motion Controller – Operation Manual. Supported Products - AH Motion Controller CPU: AHxxEMC-5A - AH series motion control modules:
AHxxEMC-5A 3-225 Name Function Data type Output range (Default value) Done True when the specified cam point is written into the cam curve. BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to Appendices for error code descriptions. DWORD 16#0~16#FFFFFFFF (0) Name Timing for shifting to True Timing for shifting to False Done When the specified cam point is written into the cam curve. When Execute shifts from True to False.
If Execute is False and Done shifts to True, Done will be True for only one period and immediately shift to False. Busy When Execute changes to True. When Done shifts to True. When Error shifts to False. Error(ErrorID) When an error occurs in the execution conditions or input values for the instruction. (error code is recorded) When Execute shifts from True to False. (error code is cleared)