Delta Electronics AH — DFB_HCnt

Chapter 3 Motion Control Instructions * Note: 2. The setting values, devices, corresponding terminals for Channel inputs: 1. Refer to Section 2.4 Data Type Unit (DUT): ENUM for explanation on using enumerations. 3. For resetting the counter value, refer to the selected DFB_Hcnt Channel and its corresponding terminals.

3_  Outputs  Outputs Update Timing 3-283 Channel Setting value Device Corresponding terminals for counting 0 200 AC00 X0.8, X0.9 1 204 AC04 X0.10, X0.11 2 208 AC08 X0.12, X0.13 3 212 AC12 X0.14, X0.15 4 216 AC16 X1.0, X1.1 5 220 AC20 X1.2, X1.3 Channel Corresponding terminals for resetting 0 X0.0 1 X0.1 2 X0.2 3 X0.3 4 X1.4 5 X1.5 Name Function Data type Output range (Default value) Valid True when the output value is valid. BOOL True/False (False) Busy True when the instruction is enabled. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to Appendices for error code descriptions.

DWORD 16#0~16#FFFFFFFF (0) CountValue Count value of the counter DWORD Continuously updates value when Valid is True. Name Timing for shifting to True Timing for shifting to False Valid  When the output value is valid; one scan cycle after Enable shifts to True.  When Enable shifts to False.  When Error shifts to True. Busy  When Enable shifts to True.  When Enable shifts to False.  When Error shifts to True.