Chapter 3 Motion Control Instructions  Troubleshooting - If an error occurs during the execution of the instruction or when the axis is in the state of Errorstop, Error will change to True and the axis will stop moving. You can refer to ErrorID (Error Code) to address the problem. - Information regarding error codes and indicators and the associated troubleshooting information are attached as Appendices for a quick reference. For the complete troubleshooting of the system, refer to AH Motion Controller – Operation Manual .  Programming Example Using channel 0 (input X0.0) with the TriggerMode from True shifting to False to obtain a timer value of 10 seconds ( TimerValue ): 3_ 1.

Set M32=ON to specify the timing mode as UP_UP, measuring the interval between rising edge and falling edge of a pulse. 2. Set M31=ON to enable channel 0 for high speed timing. 3. Trigger the rising edge of X0.0 to start timing, and trigger the falling edge of X0.0 after 10 seconds. 4. Check the value in D32 to confirm if a timed value approximately equals to 10 seconds is recorded.  Supported Products - AH Motion Controller CPU: AHxxEMC-5A - AH series motion control modules: AHxxEMC-5A 3-287