Delta Electronics AH — 9.4.2. AH02HC-5A/AH04HC-5A

AH Motion Controller – Operation Manual 9.4.2. AH02HC-5A/AH04HC-5A _9 9-68 Error code Description Corrective action 16#A805 The signal received by channel 5 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether The signal received by channel 5 exceeds the range of inputs which can be received by the hardware. 16#A806 The signal received by channel 6 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG.

Check whether the signal received by channel 6 exceeds the range of inputs which can be received by the hardware. 16#A807 The signal received by channel 7 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 7 exceeds the range of inputs which can be received by the hardware. Error code Description Corrective action 16#A001 The linear accumulation in channel 1 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR0 to ON by means of FROM/TO. 16#A002 The scale set for channel 1 exceeds the range.

Check the module parameter in HWCONFIG. The scale set for channel 1 should be in the range of 0 to 32767. 16#A003 The number of cycles set for channel 1exceeds the range. Check the module parameter in HWCONFIG. The number of cycles set for channel 1 should be in the range of 2 to 60. 16#A004 The comparison value set for channel 1 exceeds the range. Check the module parameter in HWCONFIG. The comparison value set for channel 1 should be in the range of -999999999 to 999999999. 16#A005 A limit value set for channel 1 is incorrect. Check the module parameter in HWCONFIG. A limit value of set for channel 1 should be in the range of -200000 to 200000.

16#A006 The interrupt number set for channel 1 exceeds the range. Check the module parameter in HWCONFIG. The interrupt number set for channel 1 should be in the range of 0 to 31. 16#A011 The linear accumulation in channel 1 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR28 to ON by means of FROM/TO. 16#A012 The scale set for channel 2 exceeds the range. Check the module parameter in HWCONFIG. The scale set for channel 2 should be in the range of 0 to 32767. 16#A013 The number of cycles set for channel 2 exceeds the range. Check the module parameter in HWCONFIG. The number of cycles set for channel 2 should be in the range of 2 to 60.