Delta Electronics AH — 2.2.2 Wiring Power Supply Modules

Chapter 2 Hardware Setup 2. The 110 VAC cable, the 220 VAC cable, and the 24 VDC cable should be twisted, and connected to a module within a short distance. 3. Do not bundle 110 VAC cable, the 220 VAC cable, the 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O signal cable together. Besides, it is recommended that the distance between adjacent cables should be more than 100 millimeters. 4. To prevent the surge resulting from lightning, please install a surge absorber in the way shown below. Surge absorber AC power supply 100-240V 2_ Points for attention: 1. The surge absorber and the PLC system should be grounded separately. 2.

Please select the surge absorber whose working voltage is not less than the maximum allowable input voltage.  Connecting DC power cables 1. AHPS15-5A is independently supplied with power by a DC power supply. Please separate the power cable of the DC power supply from the power cables for I/O devices and other devices. If there is much noise, connect an isolating transformer. Isolating transformer AHPS15-5A AC power supply 100-240 V 24 V DC DC power supply I/O equipment Another piece of equipment 2. The 110 VAC cable, the 220 VAC cable, and the 24 VDC cable should be twisted, and connected to a module within a short distance. 3.

Do not bundle 110 VAC cable, the 220 VAC cable, the 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O signal cable together. Besides, it is recommended that the distance between adjacent cables should be more than 100 millimeters. 4. To prevent the surge resulting from lightning, please install a surge absorber in the way shown below. Surge absorber AC power supply 100-240V 2-7 AHPS05-5A I/O equipment DC power supply I/O equipment Another piece of equipment DC power supply I/O equipment Another piece of equipment