Mitsubishi — 5.6.1 Wiring AH04AD-5A/AH08AD-5A

Chapter 5 Wiring 5.6 Wiring Analog Input/Output Modules (1) Definitions of the terminals ◆ 2-/3-wire (passive sensor): the sensor and the system share the same power circuit. ◆ 4-wire (active sensor): the sensor uses independent power supply and suggested not to share the same power circuit with the system. 5.6.1 Wiring AH04AD-5A/AH08AD-5A AG Shielded cable*1 4-wi re: Voltage i nput -10V~+10V CH 0 1M +24V 0V + - *3 CH 0 SG *4 4-wire: C urrent input -20m A~+ 20mA Shi el ded c abl e*1 CH1 AG +24V + - *2 CH1 0V *4 2- wire: C urrent input 4mA~+20mA SG AG + 24V + Shielded cable*1 CH2 1M - *2 CH2 0V SG *4 VI2- 3-wir e: Voltage i nput -10V~+10V Shielded cable*1 AG +24V CH 3 1M 0V *4 CH3 SG 3-w ire:

C ur rent input -20mA~+20mA Shielded cable*1 AG +24V + *2 CH4 V4+ 1M 0V CH4 SG *5 +15V UP 24VDC D C/DC C onverter -15V AG *1. Please use shielded cables to isolate the analog input signal cable from other power cables. *2. If the module is connected to a current signal, the terminals Vn and In+ (n=0~7) must be short-circuited. *3. If the ripple in the input voltage results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *4. Please connect the shielded cable to the terminal SG. *5.

Once AH04AD-5A is installed on a backplane, the terminal SG on AH04AD-5A and the terminal on the backplane will be short-circuited. Please connect the terminal on the backplane to the ground terminal . 5-45 V0+ I0+ 250 1M VI0- V1+ I1+ VI1- 1M V2+ I2+ 250 1M + - V3+ 250 1M I3+ VI3- - I4+ VI4- 250 1M S G ZP