AH500 Hardware Manual 5.6.2 Wiring AH08AD-5B *1. Please use shielded cables to isolate the analog input signal cable from other power cables. *2. If the ripple in the input voltage results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *3. Please connect the terminal SLD to the ground terminal . 5.6.3 Wiring AH08AD-5C +24V 0V +24V 0V +24V 0V *1. Please use shielded cables to isolate the analog input signal cable from other power cables. *2. Please connect the terminal SLD to the ground terminal .
5-46 AG ltage input 10V~+10V CH0 1M + V0+ 1M - *2 V0- SLD Shielded cable*1 AG oltage input 10V~+10V 1M CH7 + V7+ - *2 V7- 1M SLD Shielded cable*1 *3 C C AG -wire : Current inp ut -20mA~+20mA CH0 1M + I0+ 250 1M CH0 - I0- SLD -wire: Current inpu t -20mA~ +20mA AG + CH1 1M I1+ CH1 - I1- 250 1M Sh ielded cable *1 SLD -wire : Current inp ut -20mA~+20mA V AG + CH 7 1M - I7+ I7- 250 1M CH 7 Sh ielded cable *1 SLD *2 I 7- 250 1M Sh ielded cable *1 SL *2 + - I1- 250 1M SLD