Chapter 5 Wiring 5.6.4 Wiring AH04DA-5A/AH08DA-5A AC motor drive, recor der, proportioning valve CH0 -10V~+10V Voltage output *2 CH0 VO0 IO0 AG Shielded cable*1 SLD AG AC motor drive, recor der, proportioning valve C urrent output CH3 0mA~20mA CH3 VO3 AG IO3 SLD AG Shielded cable*1 *3 24VDC DC/DC +15V C onverter -15V AG *1. Please use the shielded cables to isolate the analog output signal cable from other power cables. *2. If a ripple is large for the input terminal of the load and results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *3.
Please connect the terminal SLD to the terminal SG. Once AH04DA-5A is installed on a backplane, the terminal SG on AH04DA-5A and the terminal on the backplane will be short-circuited. Please connect the terminal on the backplane to the ground terminal . 5-47 SG ZP UP