Mitsubishi — 5.6.5 Wiring AH08DA-5B

AH500 Hardware Manual 5.6.5 Wiring AH08DA-5B AC motor driv e, recorder, proportioning valve Voltage out put CH0 -10V~+10V *2 CH0 VO0 AG AG Shielded cable* 1 SG *3 Voltage out put C H7 -10V~+10V *2 CH7 VO7 Shielded cable* 1 *3 AG AG SG *4 UP 24VD C D C/DC +15V C onv erter -15V AG *1. Please use the shielded cables isolate the analog output signal cable from other power cables. *2. If a ripple is large for the input terminal of the load and results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *3. Please connect the shielded cable to the terminal SG. *4.

Once AH08DA-5B is installed on a backplane, the terminal SG on AH08DA-5B and the terminal on the backplane will be short-circuited. Please connect the terminal on the backplane to the ground terminal . 5-48 SG ZP