Mitsubishi — 5.6.7 Wiring AH06XA-5A

AH500 Hardware Manual 5.6.7 Wiring AH06XA-5A 4-wi re: Voltage Input Shielded cable * 1 AG +2 4V -1 0V~+1 0V + CH0 1M CH0 0V - *6 *3 SG AG 4-wi re: Current Input -2 0mA ~+20mA V1+ Shielded cable * 1 *2 CH1 1M +24V 0 V + - CH1 2-wir e: C urrent Input SG *6 +2 4V 4 mA~+20 mA Shielded cable * 1 CH2 AG + - *2 V2+ I2+ 2 50 1M CH2 0V *6 SG VI2- 1 M 3-wire: Voltage Input -10V~+1 0V Shielded cable * 1 A G +2 4V + - CH3 V3 + 250 1M CH3 0V *6 VI3 - I3+ 1M 3-wire:

C urrent Input -2 0mA~+2 0mA Shielded cable * 1 SG A G +24V + CH4 V4+ 1M CH4 0V SG AC motor dri ve, recorder, proportioning valve Voltage output CH0 -10V~+1 0V CH0 Shielded cable *4 *6 AG VO0 IO0 AC motor dri ve, recorder, proportioning valve SG AG Current output CH1 0 mA~20m A CH1 AG Shiel ded cable * 4 SG *6 UP 24VDC DC/DC +15 V S G * 7 ZP Conver ter -1 5V AG *1. Please isolate the analog input signal cable from other power cables. *2. If the module is connected to a current signal, the terminals V1+ and I1+ must be short-circuited, and the terminals V2+ and I2+ must be short-circuited. *3.

If the ripple in the input voltage results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *4. Please isolate the analog output signal cable from other power cables. *5. If a ripple is large for the input terminal of the load and results in the noise interference with the wiring, please connect the module to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V. *6. Please connect the shielded cables to the terminal SG. *7.

Once AH06XA-5A is installed on a backplane, the terminal SG on AH06XA-5A and the terminal on the backplane will be short-circuited. Please connect the terminal on the backplane to the ground terminal . 5-50 V0+ I0 + 250 1 M VI 0- I1+ VI1- 2 50 1 M *2 - I4 + VI4 - 250 1M *5 V O1 I O1 A G