Mitsubishi — 5.7.1 Wiring AH04PT-5A

Chapter 5 Wiring 5.7 Wiring Temperature Measurement Modules 5.7.1 Wiring AH04PT-5A *1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can be connected to an Ni100/Ni1000/Pt100/Pt1000 sensor, and should be kept separate from other power cables and cables which generate noise. Please use a three-wire temperature sensor. If users want to use a two-wire temperature sensor, O n + and I n + must be short-circuited, and O n - and I n - must be short-circuited. ( n is in the range of 0 to 3.) *2. If users want to measure resistance in the range of 0 Ω to 300 Ω, they can use a two-wire or three-wire sensor instead of a four-wire sensor. *3.

Users need to select an appropriate sensor. If an Ni100 temperature sensor, a Pt100 temperature sensor, or a resistance sensor is used, the internal excitation current is 1.53 mA. If an Ni1000 temperature sensor, or a Pt1000 temperature sensor is used, the internal excitation current is 204.8 μA. 5-51 0~300Ω Ni100/Ni1000 Pt100/Pt1000 Shielded cable *1 CH0 O I0 I O 2-Wire F 0~300Ω N i100/ Ni1000 Shielded cable *1 CH1 Pt100/ Pt1000 O I 1 I O F 3-Wire Ni100/Ni1000 Pt100/Pt1000*2 Shielded cable *1 CH3 1.53mA (Ni100P,t100, Resistor)/ 0+ 204.8uA (Pt1000)*3 + 0- ADC 0- I NA AG G 1+ + 1- 1- G AG 3+ + 3- 3- G AG O I0 0+ + I O 0- 0- F G O 1+ I 1 I + 1- O 1- F G O 3+ I 3 I + 3- O 3- F G