Mitsubishi — 5.9.1.2 Connecting a Cable to the DeviceNet Connector

AH500 Hardware Manual Example: If the station address of AH10COPM-5A is 16#26, users have to turn the knob corresponding to x16 1 to position 2, and turn the knob corresponding to x16 0 to position 6. Points for attention:  After the station address of AH10COPM-5A is changed, users have to power AH10COPM-5A again, otherwise the change will not take effect.  To prevent the address knobs on AH10COPM-5A from being scratched, please carefully use a slotted screwdriver to rotate the address knobs on AH10COPM-5A. 5.8.6.3 Function Switch The function switch on AH10COPM-5A is used to set the communication speed at which AH10COPM-5A is connected to a CANopen network.

There is a limit on the maximum communication distance to which a communication speed corresponds. Points for attention:  After users change the communication speed at which AH10COPM-5A is connected to a CANopen network, they have to power AH10COPM-5A again, otherwise the change will not take effect.  To prevent the DIP switch on AH10COPM-5A from being scratched, please carefully use a slotted screwdriver to rotate the DIP switch on AH10COPM-5A. 5.9 Wiring Remote I/O Modules 5.9.1 Wiring AHRTU-DNET-5A 5.9.1.1 DeviceNet Connector 5.9.1.2 Connecting a Cable to the DeviceNet Connector Approximately 30 mm  Remove the 30 millimeter plastic jacket of a cable with a professional tool.

Please do not damage the shielded cable when the plastic jacket is removed. 5-58 Maximum DR 2 DR 1 DR 0 I N 0 Communication DR 2 DR 1 DR 0 communication speed distance OFF OFF OFF 10 kbps 5000 m OFF OFF ON 20 kbps 2500 m OFF ON OFF 50 kbps 1000 m OFF ON ON 125 kbps 500 m ON OFF OFF 250 kbps 250 m ON OFF ON 500 kbps 100 m ON ON OFF 800 kbps 50 m ON ON ON 1 Mbps 25 m IN 0 Reserved Pin Signal Color Description 24 VDC Signal (positive pole) It is connected to a shielded cable. Signal (negative pole) 0 VDC 5 4 3 2 1 5 V+ Red 4 CAN H _ White 3 Ground - 2 CAN L _ Blue 1 V- Black