Mitsubishi — 5.10.3.3 Transistor Output Circuit

AH500 Hardware Manual 5.10.3.3 Transistor Output Circuit 5-78 AH04HC-5A Load Trigger Y0.8  Direct-current power supply  Emergency stop  Fuse  The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train output terminal of a transistor module, the output current passing through its output pull-up resistor must be greater than 0.1 A to ensure that the transistor module operates normally. A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge voltage which occurs when the load is OFF.  A bulb (incandescent lamp) is used as a DC load.

A thermistor is connected in series to absorb the surge current which occurs when the load is ON. Y0.9 can not be connected to a power supply directly. It must be connected to a load.