AH500 Hardware Manual 8.3.1 Tools Required for Inspection A screwdriver Industrial alcohol A clean cotton cloth A multimeter A thermometer A hygrometer 8.3.2 Periodic Inspection 8-4 No. Item Inspection Criterion Remedy 1 Ambient environment Ambient temperature/hu midity The ambient temperature and the ambient humidity are measured by a thermometer and a hygrometer. The ambient temperature and the ambient humidity must conform to the specifications for the modules or the backplane. If the specifications are different, the strictest specifications have high priority.
To ensure that the system operates in a stable environment, check the reason why the environment varies, and eliminate it. Atmosphere Measure corrosive gas. Corrosive gas must not be present. 2 Supply voltage Measure the AC power supply. The power supply should meet the specifications for the power supply module. Check the power supply. 3 Installation Looseness Check whether the module is loose. The module must be installed firmly. Please refer to chapter 2 for more information about installing the module. Adhesion of dirt Check the appearance. Dirt must not be present. Remove the dirt. 4 Connection Looseness of terminal screws Tighten the screws with a screwdriver.
The screws must not be loose. Further tighten the screws. Looseness of connectors Pull the connectors. The connectors must not be loose. Further tighten the screws on the connectors. 5 PLC system diagnosis Check the error logs. No new error occurs. Please refer to section 9.1.3 for more information. 6 Maximum scan time Check the state of SR413 and that of SR414 through the device monitoring table in ISPSoft. The maximum scan cycle must be within the range specified in the system specifications. Check the reason why the scan time lengthens.