Mitsubishi — 9.1.1 ERROR LED Indicator’s Being ON

AH500 Hardware Manual 9.1 Troubleshooting for CPU Modules Users can get the remedies from the tables below according to the statuses of the LED indicators and the error codes. 9.1.1 ERROR LED Indicator’s Being ON Error Description Remedy code 16#000B The program in the PLC is damaged. Download the program again. 16#000D The CPU parameter is damaged. Reset the CPU parameter, and download it. 16#0010 The access to the memory in the CPU is denied. Download the program or parameters again. If the problem still occurs, please contact the factory. 16#0011 The PLC ID is incorrect. (SM9) Please check the PLC ID. 16#0012 The PLC password is incorrect. (SM9) Please check the PLC password.

16#0014 The procedure of restoring the system can not be executed. (SM9) The contents of the system backup file are incorrect, or the file does not exist in the path specified. If the file exists and the procedure of restoring the system can not be executed, please backing up the system again. If the error still occurs, please contact the factory. (Please refer to section 7.5 in AH500 Operation Manual, and section 18.2 in ISPSoft User Manual for more information about the memory card.) 16#0015 The module table is incorrect. (SM10) The module table stored in the CPU module is incorrect.

Compare the module table in HWCONFIG with the actual module configuration, and download the module table again. 16#0016 The module setting is incorrect. (SM10) The module setting stored in the CPU module is incorrect. Check whether the version of the module inserted in the slot is the same as the version of the module in HWCONFIG. After the version of the module is updated, users can download the module setting again. 16#0017 The data register exceeds the device range. (SM10) The data register stored in the CPU module exceeds the device range. Check whether the module parameter in HWCONFIG is correct, and download the module parameter again. 16#001B Timed interrupt 0 is set incorrectly.

Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#001C Timed interrupt 1 is set incorrectly. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#001D Timed interrupt 2 is set incorrectly. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#001E Timed interrupt 3 is set incorrectly. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#001F The watchdog timer is set incorrectly. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#0020 The setting of the fixed scan time is incorrect.

Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#0021 The setting of the fixed scan time is incorrect. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#0022 The CPU parameter downloaded to the PLC is incorrect. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again.