Mitsubishi — 9.1.1 ERROR LED Indicator’s Being ON

Chapter 9 Troubleshooting 9-3 Error Description Remedy code 16#0023 The Y state (STOP RUN) section in the PLC Parameter Setting window is set incorrectly. Set the CPU parameter in HWCONFIG again, and download the CPU parameter again. 16#0026 The Communication Ratio box in the Communication Loading of Scan Time (%) section in the PLC Parameter Setting window is set incorrectly. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0027 The latching auxiliary relay range which is set is incorrect.

Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0028 The latching data register range which is set is incorrect. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0029 The latching timer range which is set is incorrect. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#002A The latching counter range which is set is incorrect.

Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#002B The range settings of the latched 32-bit counters are incorrect. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0050 The memories in the latched special auxiliary relays are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0051 The latched special data registers are abnormal.

Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0052 The memories in the latched auxiliary relays are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0053 The latched timers are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0054 The latched counters are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again.

16#0055 The latched 32-bit counters are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0056 The memories in the latched timers are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0057 The memories in the latched counters are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0058 The memories in the latched 32-bit counters are abnormal.

Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. 16#0059 The latched data registers are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again.