Mitsubishi — 9.1.2 ERROR LED Indicator’s Blinking

AH500 Hardware Manual 9.1.2 ERROR LED Indicator’s Blinking 9-4 Error Description Remedy code 16#005A The latched working registers are abnormal. Reset the CPU module or restore the CPU module to its factory settings, and then download the program and the parameters again. Error code Description Remedy 16#000A Scan timeout (SM8: The watchdog timer error) 1. Check the setting of the watchdog timer in HWCONFIG. 2. Check whether the program causes the long scan time 16#000C The program downloaded to the PLC is incorrect. Compile the program and download the program again. 16#000E The program or the parameter is being downloaded, and therefore the PLC can not run. 1.

After the program or the parameter is downloaded to the PLC, users can try to run the PLC. 2. Supply power to the PLC again. 16#0018 The serial port is abnormal. (SM9) Retry the connection. If the error still occurs, please contact the factory. 16#0019 The USB is abnormal. (SM9) Retry the connection. If the error still occurs, please contact the factory. 16#001A The contents of the system backup file (DUP) are incorrect. Generate the system backup file again. 16#0033 The communication setting of COM1 is incorrect. (SM9) 1. Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again.

16#0034 The setting of the station address of COM1 is incorrect. (SM9) 1. Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#0035 The setting of the communication type of COM1 is incorrect. (SM9) 1. Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#0038 The communication setting of COM2 is incorrect. (SM9) 1. Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#0039 The setting of the station address of COM2 is incorrect. (SM9) 1.

Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#003A The setting of the communication type of COM2 is incorrect. (SM9) 1. Check the program and the related special data registers. 2. Set the communication port parameter for the CPU module in HWCONFIG again. 16#0066 An error occurs when the system is backed up. 1. Check whether the memory card is normal, and whether the capacity of the memory card is large enough. 2. Retry the backup procedure. If the error still occurs, please contact the factory.