AH500 Hardware Manual 9.1.6 Others 9-12 Error Description Remedy code 16#000F The original program in the PLC is damaged. After users compile the program again, they can download the program again. 16#0024 There is no I/O module on a backplane. Please check whether a module exists. 16#005D The CPU module does not detect a memory card. (SM453) Check whether a memory card is inserted into the CPU module correctly. 16#005E The memory card is initialized incorrectly. (SM453) Check whether the memory card breaks down. 16#005F A nonexistent file is read from the memory card, or a nonexistent file is written to the memory card. (SM453) Check whether the file path is correct.
16#0060 The CPU module can not create a default folder in the memory card. (SM453) Check whether the capacity of the memory card is large enough, or whether the memory card breaks down. 16#0061 The capacity of the memory card is not sufficient. (SM453) Check whether the capacity of the memory card is large enough. 16#0062 The memory card is write-protected. (SM453) Check whether the memory card is write protected. 16#0063 An error occurs when data is written to the memory card. (SM453) Check whether the file path is correct, or whether the memory card breaks down. 16#0064 A file in the memory card can not be read.
(SM453) Check whether the file path is correct, or whether the file is damaged. 16#0065 A file in the memory card is a read-only file. (SM453) Users need to set the file so that the file is not a read-only file. 16#1801 There is no interrupt service routine in the CPU module. Check whether there is a corresponding interrupt task (24V low voltage interrupt service routine) in the program. 16#600A TCP connection failure (SM1090) 1. Check the actual network configuration, and check whether the number of TCP connections exceeds the upper limit supported by the CPU module. 2. Retry the TCP connection later. (This error does not cause the PLC to stop running.
Users can perform the corresponding remedy by means of the related flag in the program.) 16#600B UDP connection failure (SM1091) 1. Check the actual network configuration, and check whether the number of UDP connections exceeds the upper limit supported by the CPU module. 2. Retry the TCP connection later. (This error does not cause the PLC to stop running. Users can perform the corresponding remedy by means of the related flag in the program.) 16#600C The TCP socket has been used. (SM1109) 1. Check whether the actual data access results in the use of the same socket. 2. Change the socket number, or retry the socket later. (This error does not cause the PLC to stop running.
Users can perform the corresponding remedy by means of the related flag in the program.) 16#600D The RJ45 port is not connected. Check the communication cable. 16#600E An RJ45 port on AH10EN-5A is not connected to a network cable. Please check whether AH10EN-5A is connected to a network cable.