Chapter 9 Troubleshooting 9-13 Error Description Remedy code 16#6100 The email connection is busy. (SM1113) Retry the email connection later. (This error does not cause the PLC to stop running. Users can perform the corresponding remedy by means of the related flag in the program.) 16#6104 The attachment in the email does not exist. (SM1113) Check whether the attachment exists in the memory card. 16#6105 The attachment in the email is oversized. (SM1113) Check the size of the file which is specified as the attachment. If the size is over 2 MB, the file can not be specified as the attachment. 16#6107 There is an SMTP server response timeout. (SM1113) 1.
Check whether the status of the SMTP server is normal. 2. Retry the sending of the email later. (This error does not cause the PLC to stop running. Users can perform the corresponding remedy by means of the related flag in the program.) 16#6201 The local communication port set in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6202 The remote communication port set in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again.
16#6203 The device from which the data is sent in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6204 The transmitted data length set in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6205 The data which is sent through the TCP socket exceeds the device range. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again.
16#6206 The device which receives the data in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6207 The received data length set in the TCP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again. 16#6208 The data which is received through the TCP socket exceeds the device range. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again.
16#620A The local communication port set in the UDP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG again.