AH500 Hardware Manual 9-16 Error Description Remedy code 16#7402 The size of a packet exceeds the maximum data length. Please check the contents of the packet sent by the remote device. 16#7404 Packet format error Please check the contents of the packet sent by the remote device. 16#7405 The number of bytes is incorrect. Please check the contents of the packet sent by the remote device. 16#7406 Checksum error Please check the contents of the packet sent by the remote device. 16#7407 There are non-ASCII characters in a command. Please check the contents of the packet sent by the remote device. 16#7408 The PLC is running.
When the PLC is running, data such as a program and CPU parameters can not be downloaded to the PLC. 16#740A Data is being written to the memory in the PLC or data fails to be written to the memory in the PLC. Data is being written to the flash memory/SD card. Please try again later. 16#740B The CPU module is being reset, or the values in the laching devices are being cleared. The CPU module is being reset, or the values in the laching devices are being cleared. Please try again later. 16#740C The backplane number in a communication command is incorrect. Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory.
16#740D The slot number in a communication command is incorrect. Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory. 16#740E An error occurs when the the data in the memory in the PLC is cleared. Please try agin. If the error still occurs, please contact the factory. 16#740F Communication timeout Please check whether the remote device operates normally. 16#7410 The function code in a reply command is incorrect. Please check the contents of the packet sent by the remote device. 16#7412 Owing to the fact that SW1 is ON, data can not be downloaded to the CPU module. Please make sure that SW1 is OFF.
16#757D The remaining number of PLC password guesses is 0. Please power the CPU module again. 16#757E The PLC password entered is incorrect. Please check whether the PLC password entered is correct. 16#8105 The contents of the program downloaded are incorrect. The program syntax is incorrect. 1. Check whether the program syntax which is not supported by the CPU module is used, and check whether the version of the firmware has its special limitation. 2. Check whether the version of ISPSoft used to create the program is the same as the version of ISPSoft used now. 16#8106 The contents of the program downloaded are incorrect. The length of the execution code exceeds the limit. 1.
Shorten the length of the program, and download the program again. 2. Check whether the version of ISPSoft used to create the program is the same as the version of ISPSoft used now.