Chapter 9 Troubleshooting 9-15 Error Description Remedy code 16#6309 The remote device in the Ether Link does not respond after the timeout period. 1. Check whether the CPU module in the Ether Link operates normally. 2. Check whether the CPU modules are connected normally. 16#6400 The number of TCP connections reaches the upper limit, or the flag which is related to the sending of the data is not set to ON. 1. Check whether the flag which is related to the sending of the data in the program is modified. 2. Retry the setting of the flag and the sending of the packet. 16#6401 The remote device aborts the connection. Check whether the remote device support the Modbus port (502).
16#6402 There is no response from the remote device after the timeout period. Check whether the remote device operate normally. 16#6403 The remote IP address used in the applied instruction is illegal. Check whether the program is correct. 16#6404 The Modbus function code not supported is received. Check the command transmitted from the remote device. 16#6405 The number of data which will be received is not consistent with the actual length of the data. Check the command transmitted from the remote device. 16#6501 The remote device involved in the data exchange does not respond after the timeout period.
(SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally. 16#6502 The remote device involved in the data exchange does not respond correctly. (SM828~SM955) Check the device whose connection number corresponds to the error flag, and check whether it is connected normally. 16#6600 The network number which receives the command exceeds the range. Check the command transmitted from the remote device. 16#6601 The network is undefined in the network configuration parameter. Check the network configuration in NWCONFIG, and download it again. 16#6604 The number of routing connections reaches the upper limit.
Resend the packet later. ((This error does not cause the PLC to stop running. Users can perform the corresponding remedy by means of the related flag in the program.) 16#6605 The unexpected packet is received. Check the command transmitted from the remote device. 16#6606 There is a routing response timeout. 1. Check the network configuration in NWCONFIG. 2. Check whether the setting of the communication timeout conform to the practical application. 16#6700 An error occurs when a Modbus TCP data exchange is initialized. Please check setting values, and download them again.
16#6701 Modbus TCP data exchange timeout Please check whether the remote device supports the Modbus communication protocol. 16#6702 The data received by means of a Modbus TCP data exchange is incorrect. Please check whether the remote device supports the Modbus communication protocol. 16#7002 The CPU module does not support the function. Please check the version of the firmware installed on the CPU module. 16#7203 Invalid access code Please check the contents of the packet sent by the remote device. 16#7401 Function code error Please check the contents of the packet sent by the remote device.