AH500 Hardware Manual 9-18 16#853C An I/O module does not exist. Check whether the module configuration in HWCONFIG is correct. 16#854B An I/O module is not configured. Check whether the module configuration in HWCONFIG is correct. 16#854C An I/O module does not exist. Check whether the module configuration in HWCONFIG is correct. 16#8572 The checksum of the module configuration table is incorrect. Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory. 16#8576 The checksum of the module parameter setting is incorrect.
Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory. 16#857A The checksum of the module parameter mapping table is incorrect. Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory. 16#85E1 An I/O interrupt number is incorrect. Please check the version of the firmware installed on the CPU module and the version of ISPSoft, and contact the factory. 16#85E2 IAn I/O interrupt service routine does not exist. Check whether the corresponding interrupt service routine is downloaded to the CPU module. 16#860F System restoration error 1.
The contents of the system backup file are incorrect, or the file does not exist in the path specified. 2. If the file exists and the procedure of restoring the system can not be executed, please backing up the system again. 3. If the error still occurs, please contact the factory. 16#8611 No memory card exists, or the memory card format is incorrect. No memory card is detected. Please format the memory card, and try again. 16#8612 An error occurs when data is accessed from the memory card, or the memory card is in read-only mode. Please make sure that the memory card is not in read-only mode, and try again. 16#8F03 A node number is undefined.
Modify the instruction and the network parameters, and download them again. 16#9A01 The setting of the data exchange for slave 1 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A02 The setting of the data exchange for slave 2 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A03 The setting of the data exchange for slave 3 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again.
16#9A04 The setting of the data exchange for slave 4 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A05 The setting of the data exchange for slave 5 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A06 The setting of the data exchange for slave 6 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A07 The setting of the data exchange for slave 7 in the PLC Link is incorrect. (SM1590) 1.
Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again.