Chapter 9 Troubleshooting 9-19 Error Description Remedy code 16#9A08 The setting of the data exchange for slave 8 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A09 The setting of the data exchange for slave 9 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A0A The setting of the data exchange for slave 10 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again.
16#9A0B The setting of the data exchange for slave 11 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A0C The setting of the data exchange for slave 12 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A0D The setting of the data exchange for slave 13 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A0E The setting of the data exchange for slave 14 in the PLC Link is incorrect.
(SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A0F The setting of the data exchange for slave 15 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A10 The setting of the data exchange for slave 16 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A11 The setting of the data exchange for slave 17 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2.
Set the PLC Link parameter in HWCONFIG again. 16#9A12 The setting of the data exchange for slave 18 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A13 The setting of the data exchange for slave 19 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A14 The setting of the data exchange for slave 20 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again.
16#9A15 The setting of the data exchange for slave 21 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A16 The setting of the data exchange for slave 22 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A17 The setting of the data exchange for slave 23 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A18 The setting of the data exchange for slave 24 in the PLC Link is incorrect.
(SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again. 16#9A19 The setting of the data exchange for slave 25 in the PLC Link is incorrect. (SM1590) 1. Check the program and the related special data registers. 2. Set the PLC Link parameter in HWCONFIG again.