Mitsubishi — 9.2.2 Troubleshooting for AH02HC-5A/AH04HC-5A

AH500 Hardware Manual 9.2.2 Troubleshooting for AH02HC-5A/AH04HC-5A 9-30 Error Description Remedy code 16#A803 The signal received by channel 3 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 3 exceeds the range of inputs which can be received by the hardware. 16#A804 The signal received by channel 4 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 4 exceeds the range of inputs which can be received by the hardware.

16#A805 The signal received by channel 5 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 5 exceeds the range of inputs which can be received by the hardware. 16#A806 The signal received by channel 6 exceeds the range of inputs which can be received by the hardware. (The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 6 exceeds the range of inputs which can be received by the hardware. 16#A807 The signal received by channel 7 exceeds the range of inputs which can be received by the hardware.

(The ERROR LED indicator is OFF.) Check the module parameter in HWCONFIG. Check whether the signal received by channel 7 exceeds the range of inputs which can be received by the hardware. Error Description Remedy code 16#A001 The linear accumulation in channel 0 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR0 to ON by means of FROM/TO. 16#A002 The prescale value for channel 0 exceeds the range. Check the module parameter in HWCONFIG. The prescale value for channel 0 should be within the range between 0 and 32767. 16#A003 The moving average for channel 0 exceeds the range. Check the module parameter in HWCONFIG.

The moving average for channel 0 should be within the range between 2 and 60. 16#A004 The comparison value for channel 0 exceeds the range. Check the module parameter in HWCONFIG. The comparison value for channel 0 should be within the range between -999999999 and 999999999. 16#A005 The limit value of the alarm output for channel 0 is incorrect. Check the module parameter in HWCONFIG. The limit value of the alarm output for channel 0 should be within the range between -200000 and 200000. 16#A006 The interrupt number for channel 0 exceeds the range. Check the module parameter in HWCONFIG. The interrupt number for channel 0 should be within the range between 0 and 31.

16#A011 The linear accumulation in channel 1 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR28 to ON by means of FROM/TO. 16#A012 The prescale value for channel 1 exceeds the range. Check the module parameter in HWCONFIG. The prescale value for channel 1 should be within the range between 0 and 32767.