AH500 Hardware Manual 9-32 Error Description Remedy code 16#A002 The subroutine has no data. A program should be written in the subroutine. 16#A003 CJ, CJN, and JMP have no matching pointers. Write the pointers which match CJ, CJN, and JMP respectively. 16#A004 There is a subroutine pointer in the main program. The subroutine pointer can not be in the main program. 16#A005 Lack of the subroutine The nonexistent subroutine can not be called. 16#A006 The pointer is used repeatedly in the same program. The pointer can not be used repeatedly in the same program. 16#A007 The subroutine pointer is used repeatedly. The subroutine pointer can not be used repeatedly.
16#A008 The pointer used in JMP is used repeatedly in different subroutines. The pointer used in JMP can not be used repeatedly in different subroutines. 16#A009 The pointer used in JMP is the same as the pointer used in CALL. The pointer used in JMP can not be the same as the pointer used in CALL. 16#A00B Target position (I) of the single speed is incorrect. The target position (I) of the single speed should be set correctly. 16#A00C Target position (II) of the single-axis motion is incorrect. Check whether target position (II) of the single-axis motion and target position (I) of the single-axis motion are in opposite directions.
16#A00D The setting of speed (I) of the single-axis motion is incorrect. Set the speed of the single-axis motion. 16#A00E The setting of speed (II) of the single-axis motion is incorrect. The setting value can not be zero. 16#A00F The setting of the speed (VRT) of returning to zero is incorrect. Set the speed of returning to zero properly. (The setting value can not be zero.) 16#A010 The setting of the deceleration (VCR) of returning to zero is incorrect. Set the speed of returning to zero. The deceleration should be less than the speed of returning to zero. (The setting value can not be zero.) 16#A011 The setting of the JOG speed is incorrect. The setting value can not be zero.
16#A012 The positive pulses generated by the single-axis clockwise motion are inhibited. The error occurs because the limit sensor is triggered. Check the status of the limit sensor, and check whether the motor operates normally. 16#A013 The negative pulses generated by the single-axis counterclockwise motion are inhibited. The error occurs because the limit sensor is triggered. Check the status of the limit sensor, and check whether the motor operates normally. 16#A014 The limit switch is reached. The error occurs because the limit sensor is triggered. Check the status of the limit sensor, and check whether the motor operates normally.
16#A015 The device which is used exceeds the device range. Use the device which does not exceed the device range. 16#A017 An error occurs when the device is modified by a 16-bit index register/32-bit index register. Use the 16-bit index register/32-bit index register which does not exceed the device range. 16#A018 The conversion into the floating-point number is incorrect. Modify the operation to prevent the abnormal number from occurring. 16#A019 The conversion into the binary-coded decimal number is incorrect. Modify the operation to prevent the abnormal number from occurring.
16#A01A Incorrect division operation (The divisor is 0.) Modify the operation to prevent the divisor from being zero. 16#A01B General program error Modify the program to make the syntax correct. 16#A01C LD/LDI has been used more than nine times. Modify the program to prevent LD/LDI from being used more than nine times.