Mitsubishi — 9.2.8 Troubleshooting for AH10PFBM-5A

AH500 Hardware Manual 9.2.8 Troubleshooting for AH10PFBM-5A 9-36 Error Description Remedy code 16#A0FA The node ID of AH10DNET-5A is the same as that of the slave set in the scan list. 1. Set the node ID of AH10DNET-5A again. The new node ID can not be the same as the node ID of the slave set in the scan list. Supply power to AH10DNET-5A again. 2. Put no slave in the scan list, and download the blank scan list to AH10DNET-5A through the simulated online mode in the software. Supply power to AH10DNET-5A again. 16#A0FB An error occurs in the data exchange between AH10DNET and AH CPU Supply power to AHCPU and 10DNET again. If the error still occurs, please contact the factory.

16#A0FC Errors occur on the slave station or the modules connected to the backplane of AHRTU-DNET 1. Check whether the node ID of the slave changes. 2. Check whether the communication cable is disconnected or loose. 3. Check whether the length of the cable is larger than the maximum transmission distance. If the length of the cable is larger than the maximum transmission distance, the stability of the system can not be ensured. Refer to AH500 module manual section 10.3.3 for more information on the acceptable transmission distance. 4. Check whether the modules on the backplane are normal. 5. Check whether AHRTU-DNET connected to the backplane is normal.

Error Description Remedy code 16#A001 The configuration in the master module is empty. Download the appropriate configuration again. 16#A003 The master station enters the test mode. Just repower it. 16#A005 A timeout occurs when chips inside the master station communicate. Download the appropriate configuration again. If the error still occurs, please contact the factory. 16#A00B A timeout occurs when AH10PFBM-5A exchanges data exchange with a PLC. Repower AH10PFBM-5A . If the error still occurs, please contact the factory. 16#A402 PLC does not assign the I/O mapping area to the master. Assign the appropriate I/O mapping area to the master via ISPSoft.

16#A404 Master initializing error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A406 Internal storage unit error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A407 Data exchange unit error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A408 Master serial number detection error Contact the factory if the error still exists after repowering AH10PFBM-5A. 16#A4E2 AH10PFBM-5A detects that one slave is offline. 1. Detect if the PROFIBUS-DP bus connection is proper. 2. Detect if both ends of the network have connected the terminal resistors respectively.

16#A4E6 The master station detects that an error occurs in a module Please check the modules connected to AHRTU-PFBS-5A.