Chapter 9 Troubleshooting 9.2.9 Troubleshooting for AH10PFBS-5A 9.2.10 Troubleshooting for AH10COPM-5A 9-37 Error code Description Remedy connected to AHRTU-PFBS-5A. Error code Description Remedy 16#A4F0 The node address of AH10PFBS-5A exceeds the valid range. Set the node address of AH10PFBS-5A between 1~125. 16#A4F1 Internal hardware error If the error still exists after repowering AH10PFBS-5A, replace it with a new one. 16#A4F2 Parameter error Check if the GSD file AH10PFBS-5A is using is correct. 16#A4F3 Configuration error Check if the GSD file AH10PFBS-5A is using is correct. 16#A4F4 GPIO detection error If the error still exists after repowering AH10PFBS-5A, replace it with a new one.
16#A4F5 AH10PFBS-5A enters the mode of factory test. Repower AH10PFBS-5A after setting its node address between 1~125. 16#A4F6 AH10PFBS-5A has not been connected to the PROFIBUS-DP network. PROFIBUS-DP master has not configured AH10PFBS-5A slave or the configured node address of AH10PFBS-5A is inconsistent with that of the actually connected one. Check if the communication cable between AH10PFBS-5A and PROFIBUS-DP master is in normal status. Ensure that AH10PFBS-5A slave has been configured to PROFIBUS-DP master and the configured node address of AH10PFBS-5A is consistent with that of the actually connected one. Check if PROFIBUS-DP master works normally.
Error code Description Remedy 16#A0B0 AH10COPM-5A does not send a heartbeat message after a set period of time. Check whether the bus cable on the CANopen network created is connected correctly. 16#A0B1 The length of a PDO that a slave station sends is not the same as the length of the PDO set in the node list. Set the length of the PDO in the slave station again, and then download the setting to AH10COPM-5A. 16#A0B2 The master station selected does not send a node guarding message after a set period of time. Check whether the bus cable on the CANopen network created is connected correctly. 16#A0E0 AH10COPM-5A receives an emergency message from a slave station.
Use the function block CANopen EMCY to read relevant _ information. 16#A0E1 The length of a PDO that a slave station sends is not the same as the length of the PDO set in the node list. Set the length of the PDO in the slave station again, and then download the setting to AH10COPM-5A. 16#A0E2 AH10COPM-5A does not receive a PDO from a slave station. Make sure that the PDOs in the slave station are set correctly.