Mitsubishi — 3.6.1 General Specifications

AH500 Hardware Manual  UB-10-OR16B AH series terminals: (only applicable for AH series) 3.6 Specifications for Analog Input/Output Modules 3.6.1 General Specifications  AH04AD-5A/AH08AD-5A/AH08AD-5B/AH08AD-5C Electrical specifications Functional specifications 3-40 GND +24V C0 Y0.0 Y0.1 Y0.2 Y0.3 C1 Y0.4 Y0.

5 Y0.6 Y0.7 C2 Y0.8 Y0.9 Y 0.10 Y0.11 C3 Y0.12 Y0.13 Y0.14 Y0.15 Module name AH04AD-5 A AH08AD-5A AH08AD-5B AH08AD-5C Number of inputs 4 8 8 8 Analog-to-digital Voltage inp Current inp ut/ Voltage input/ ut Current input Voltage input Current input conversion Supply voltage 24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%) Connector type Removable terminal block Conversion time 150 μs/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/an optocoupler, but the analog channels are not isolated from one another. Isolation between a digital circuit and a ground: 500 VDC Isolation between an analog circuit and a ground:

500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and a ground: 500 VDC Isolation Weight 200g Analog-to-digital Voltage input conversion Rated input range -10 V~10 V 0 V~10 V ±5 V 0 V~5 V 1 V~5 V Hardware input -10.1 V~10.1 V -0.1 V~10.1 V -5.05 V~5.05 V -0.05 V~5.05 V 0.95 V~5.05 V range Fiducial error ±0.1% (Room temperature) (The umber of input voltages which are averaged is 100.) Fiducial error ±0.45% (Full temperature range) (The number of input voltages which are averaged is 100.) Linearity error ±0.07% (Room