Chapter 9 Ethernet Communication Module AH10/15EN CR#650 ~ CR#659: Setting up the data point for the database of the slave station Example: AH15EN-5A as a slave, when creating data M_SP IOA 100 ~ IOA 104 to the database and corresponding to M100 ~ M104 of the CPU register, users can input the values according to the table below and trigger to create. The same rule applies to 2 nd ~ 16 th remote devices. Refer to section 9.3.5 for details on type id parameters and codes. CR#672 ~ 684: Setting up the starting position of the corresponding CPU register for the 1 st connection of the type id of the remote device. One word represents one type id.
9-13 CR Number Value in the control register Description #645 K100 IOA 100 (information object address) of the remote device #646 K1 1:ON,0:OFF #647 K0 #620 K45 Single command code CR Number Value in the control register Description #650 K5 Add 5 data points #651 K1 Type identification, 1: M SP NA 1 _ _ _ #652 K100 The starting position of IOA is 100. #653 K0 #654 K1 Group mask, 1: group 1 station interrogation #655 K0 Flags = 0 #656 K0 Default value = 0 #657 K0 #658 K100 The starting position of CPU register is M100. #659 K1 1:
trigger to create CR Number Description #672 Single-point information corresponds to the starting position of M device #673 Double-point information corresponds to the starting position of M device #674 Step position information corresponds to the starting position of D device #675 Bitstring of 32 bit corresponds to the starts position of D device #676 Measured value, normalized value corresponds to the starting position from D500 #677 Measured value, scaled value corresponds to the starting position of D device #678 Measured value, short floating point value corresponds to the starting position of D device #679 Integrated totals corresponds to the starting position of D device #680 Event of protection equipment corresponds to the starting position of D device #681 Packed start events of protection equipment corresponds to the starting