Chapter 12 Network Module AH10PFBM Double click the 10PFBM icon in the HWCONFIG window; the “Parameter Setting” dialog box pops up and then click “Normal Exchange Area” tab as below. Explanation of corresponding registers in the normal exchange area in AH10PFBM-5A. 12-55 Item Content Description Treatment value Network state 0 Not found Check if the hardware configuration for AH PLC CPU has configured the master. Refer to section 15.1 on PLC hardware configuration. 1 Offline The master has not configured the slave. Add the slave and then download the configuration once again. 2 STOP Select “Start Communication” from “Additional Functions” in the software.
3 Idle (PLC CPU is in STOP state) Restore PLC to RUN or check if the hardware configuration for PLC CPU is consistent with the actual configuration of the rack. 4 RUN No action needed. Network error count - How many times for the slave which is offline on the network since the master is powered on. 1. Check if the PROFIBUS DP bus is connected correctly. 2. Check if either end of the network is added with the terminal resistor. System error code - Consistent with the PROFIBUS network error codes in the PLC system log that is read via ISPSoft. For more details, refer to section 13.2.2.4. - The high word of communicator - Reserved -