Chapter 12 Network Module AH10PFBM 12.7.4 Error Codes of PROFIBUS Network on PLC System Log Read via ISPSoft Select menu “PLC”-> “System Log” to check the system log when ISPSoft is in monitor state. Explanation of error codes of PROFIBUS network on the PLC system log. 12-57 Error Explanation Treatment code 16#A4E2 AH10PFBM-5A detects that one slave is offline. 1. Detect if the PROFIBUS DP bus connection is proper. 2. Detect if both ends of the network have connected the terminal resistors respectively. 16#A4E6 An error of some modules connected to AHRTU-PFBS- 5A is detected by the master. Please check the modules connected to AHRTU- PFBS-5A.
16#A001 The configuration in the master module is empty. Download the appropriate configuration. 16#A402 PLC does not assign the IO mapping area to the master Assign the appropriate IO mapping area to the master via ISPSoft 16#A003 Master enters test mode Just re-power it. 16#A404 Master initializing error Contact the factory if the error still exists after re- powering 10PFBM. 16#A005 Timeout for the communication between chips inside master Contact the factory if the error still exists after re- downloading the appropriate configuration. 16#A406 Internal storage unit error Contact the factory if the error still exists after re- powering 10PFBM.
16#A407 Data exchange unit error Contact the factory if the error still exists after re- powering 10PFBM. 16#A408 the master serial number detection error Contact the factory if the error still exists after re- powering 10PFBM. 16#A00B Timeout for the data exchange with PLC Contact the factory if the error still exists after re- powering 10PFBM.