Chapter 14 Remote I/O Communication Module AHRTU-PFBS 2. Conversion between analog modules and digital modules that AHRTU-PFBS supports: When the input / output mode of the analog module is positive voltage or positive current, the corresponding digital value is 0 ~32000; for example, if the modes are 0V~10V and 4mA~20mA, the corresponding digital values are both 0~32000. When the input /output mode of the analog module is negative voltage or negative current, the corresponding digital value is -32000~32000; for example, the modes are -10V~+10V, and -20mA~20mA, the corresponding digital values are both -32000~32000. 3.
AHRTU-PFBS-5A must be installed to the CPU slot of the main rack; supports maximum 8 racks including 1 main rack and maximum 7 extension racks and 48 I/O modules. 14-11 Special module model Mapping parameter (length) Arrangement of mapping parameters in each channel (Length) AH04AD-5A Digital value converted from the analog quantity of input CH0~CH3 of AH04AD(Length=8) Digital value in Byte0~ Byte1 that the input channel 0 corresponds to(Length=2) Digital value in Byte2~ Byte3 that the input channel 1 corresponds to(Length=2) Digital value in Byte4~ Byte5 that the input channel 2 corresponds to(Length=2) Digital value in Byte6~ Byte7 that the input channel 3 corresponds to(Length=2)