Kaiyi — 14.6 GSD File

AH500 Module Manual 4. The total lengths of input and output mapping for all configured I/O modules are both 244 bytes at most and the total length of all configured I/O module parameters is maximum 244 bytes. Therefore, different input and output mapping lengths of different modules and parameter lengths will decide the number of the configured I/O modules. 14.5 Transmission Distance and Baud Rate The PROFIBUS DP baud rate ranges from 9.6Kbps to 12Mbps. The transmission distance depends on the baud rate. The range of the transmission distance is between 100m to 1,200m. The baud rate and the corresponding transmission distance that AHRTU-PFBS-5A supports are shown in the following table.

14.6 GSD File The GSD file, a text file, is used to recognize the PROFIBUS device (master or slave). GSD file includes all necessary data information for configuration of one slave in the standard PROFIBUS DP master. The GSD file usually contains the supplier’s information, supported transmission speed and available I/O information. Before using AHRTU-PFBS-5A, import its GSD file to the configuration software of the PROFIBUS DP master. After the GSD file is imported, AHRTU-PFBS-5A and other configuration options will show up in the master configuration software. The GSD file of AHRTU-PFBS-5A can be downloaded from the following Delta website.

http://www.deltaww.com/ 14-12 Baud 9.6k 19.2k 93.75k 187.5k 500k 1.5M 3M 6M 12M rate(bps) Transmission 1200 1200 1200 1 000 400 200 100 100 100 distance(m)