Kaiyi — 14.7.2 Configuration of PROFIBUS DP Network

AH500 Module Manual Explanation of the options above 14-22 Name Setting Explanation I/O module error Stop I/O exchange & report fault When an error in some I/O module connected to AHRTU-PFBS-5A occurs, AHRTU-PFBS-5A stops the data exchange between other I/O modules and the master and meanwhile reports the E4 error. Continue & report fault When an error in some I/O module connected to AHRTU-PFBS-5A occurs, other I/O modules continue running and AHRTU-PFBS-5A reports the E4 fault. Loss comm with master I/O module stops running When the communication between AHRTU-PFBS-5A and the master is disrupted, AHRTU-PFBS-5A stops all I/O modules running and reports the F6 error.

I/O module continues running When the communication between AHRTU-PFBS-5A and the master is disrupted, AHRTU-PFBS-5A continues running and reports the F6 error. DIO data storage format Little Endian Little Endian: valid only for digital modules. Take the 32-point output module for example. If AH10PFBM-5A is the master and D6000 & D6001 correspond to the 32-point output module, in D6000, bit0~bit7 correspond to Y0.0~Y0.7 and bit8~bit15 to Y0.8~Y0.15; in D6001, bit0~bit7 correspond to Y1.0~Y1.7 and bit8~bit15 to Y1.8~Y1.15.

If a Siemens PLC is used as the master and PQD256(containing PQB256, PQB257, PQB258 and PQB259) corresponds to the 32-point output module, PQB256 corresponds to Y0.8~Y0.15, PQB257 to Y00.~Y0.7, PQB258 to Y1.8~Y1.17, PQB259 to Y1.0~Y1.7. All digital input and output modules follow the corresponding relationships above. The option is recommended to select when AH10PFBM-5A is the master. Big Endian Big Endian: valid only for digital modules. Take the 32-point output module