Chapter 14 Remote I/O Communication Module AHRTU-PFBS As shown in the following figure, the option “Slave receives no data in Clear Mode” is selected as the “Fail-Safe Behavior” when the master is in STOP state. 14-23 Name Setting Explanation for example. If a Siemens PLC is used as the master and PQD256(containing PQB256, PQB257, PQB258 and PQB259) corresponds to the 32-point output module, PQB256 corresponds to Y0.0~Y0.7, PQB257 to Y0.8~Y0.15, PQB258 to Y1.0~Y1.7, PQB259 to Y1.8~Y1.15.
If AH10PFBM-5A is the master and D6000 & D6001 correspond to the 32-point output module, in D6000, bit0~bit7 correspond to Y0.8~Y0.15 and bit8~bit15 to Y0.0~Y0.7; in D6001, bit0~bit7 correspond to Y1.8~Y1.15 and bit8~bit15 to Y1.0~Y1.7. The option is recommended to select when the Siemens PLC is used as the master. Master in Clear mode I/O module continues running AHRTU-PFBS-5A continues running when the option “Slave receives no data in Clear Mode” under “Fail-Safe Behavior” is selected and meanwhile the master is in STOP state.
I/O module stops running AHRTU-PFBS-5A stops all I/O modules from running when the option “Slave receives no data in Clear Mode” under “Fail-Safe Behavior” is selected and meanwhile the master is in STOP state.