Chapter 14 Remote I/O Communication Module AHRTU-PFBS Setting of AH08DA-5B After configuring AH08DA-5B, refer to Figure 5 for the related parameters setting. Figure 5 Explanation of the options above 14-31 Name Setting Explanation rack 0x01 The number of the rack where the I/O module are placed (Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11.) slot 0x04 The number of the slot on the rack where the I/O module is. (Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11). CH0~CH7 output mode disable -10V~+10V 0V~10V 5V~+5V 0V~+5V 1V~+5V The output channel mode of AH08DA-5B is disabled by default.
Mode: disable Mode: -10V~+10V Mode: 0V~10V Mode: -5V~+5V Mode: 0V~+5V Mode: 1V~+5V CH0~CH7 output hold disable/enable Output hold options Enable: the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.