Kaiyi — 14.7.2 Configuration of PROFIBUS DP Network

AH500 Module Manual  Setting of AH08DA-5C After configuring AH08DA-5C, refer to Figure 6 for the related parameters setting. Figure 6 Explanation of the options above 14-32 Name Setting Explanation rack 0x01 The number of the rack where the I/O module is (Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11.) slot 0x05 The number of the slot on the rack where the I/O module is. (Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11). CH0~CH7 output mode disable 0mA~20mA 4mA~20mA The output channel mode of AH08DA-5C is disabled by default. Mode: disable Mode:

0mA~20mA Mode: 4mA~20mA CH0~CH7 output hold disable/enable Output hold options: Enable: the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.